Specification
Output Capacity (KVA )
80 KVA
Output Capacity (KW )
72 KW
Output Power Factor
0.9 Power Factor
Other Output Voltage
380 Or 400 Volt
Efficiency at Full Load
> 93 %
Output Frequency (sync to mains)
50/60Hz +/- 3 Hz
Output Voltage THD
< 3% linear load and <5% non-linear load
Output Connections
Hard Wire 5-wire (3PH + N + G)
Bypass
Built-in Static Bypass
Overload Capacity
150% for 1 minute 125% for 10 minutes
Output Waveform type
Sine Wave
Other Input Voltage
385 Or 415 Volt
Input frequency
50 Or 60 Hz
Input frequency Range
45 - 55 Hz
Input Voltage Range for Main Operations
340 - 470 Volt
Input Connections
Hard Wire 5-wire (3PH + N + G)
Battery DC Bus
384 - 480 VDC
Battery Type Compatibility
SMF Battery
Battery Circuit Breaker
Optional
Approved Battery Capacity (AH)
65 - 200 Amp.
Maximum Charger Capacity
20 Amp.
Communication & Management
Control panel
LCD Display
Interface Port(s)
RS-232, USB
Audible Alarm
Audible and visible alarms prioritized by severity
Isolation Transformer
Optional
Flexible Battery Option
Yes
Paralleling Kit for Synchronising
Optional
Technology
Double Conversion Online
Filtering
Full time multi-pole noise filtering : 0.3% IEEE surge let-through : zero clamping response time : meets UL 1449
Operating Temperature
0 - 40 °C
Operating Relative Humidity
0 - 95 %
Other Environmental Compliance
Compliant
Compliance
EN/IEC 62040-1, IEC 62040-2, IEC 62040-3, IEC 62040-4
Approvals
CE, EAC, IEC 62040-1-1, IEC 62040-2, IEC 62040-3, IEC 62040-4, ISTA 2B, RCM, WEEE